FEATURES:
• Convenient 3/4" anchoring holes allow easy
access for bolting enclosure to floor
• The M6 rails are infinitely adjustable front to
rear via slots and sliding nuts. A 7/16" socket
is required to loosen the bolt and make
adjustment.
• Maximum rail spacing, front to rear, is 36";
three pair of rails are included
• These rails can accept multi-vendor "server
specific" side mounting adapters.
• Reversible rails are marked with U count. The
number "0" is at the center of the rail, running
22 up and 22 down the rail.
• Cinch strap/wire tie locations on side of rails
both horizontal and vertical.
• Frames accepts standard Enhanced Series
top and bottom panels
• The front and rear doors and top panel have
mesh panel inserts for ventilation.
• Same door options as the Enhanced Series
Enclosures.
• Generous cable access
• Cables can enter the enclosure through3 locations:
• 24"W x 3.75"D opening in the bottom rear
• 13.5"W x 4"D opening next to the rear
opening
• The standard center opening of
11.75"W x 14.75"D
• Cable loop lance located at the bottom rear
opening allow you to secure your incoming
cable.
• The side of the rear corner posts have three
2.5" x 6" knockouts
• Top back of the enclosure has two 2.5" x 6"
knockouts
• Networking of cabinet frames is accomplished
by bolting them together through holes in the
side faces of the corner posts with common
1/4-20 hardware.
• Split side panels, lighter for easier handling
• Increased strength with center side posts
between side panels

Close this window to return

                                  


 

• CME-42ES: optional front & rear vertical cable management run in each rear corner post
• HCM-W29ES: optional horizontal cable management spanning left to right in the top
front/rear with "waterfall" edges to protect cables.
• Up to four standard GLCC vertical power strips can be mounted to the two rear corner
posts; two per post with optional bracket, part number PSB-ES2
• Up to 24 standard 1U x 19" EIA PDU's can be mounted in the spaces between the EIA
rails and side panels; 12 per side. (Optional PDU brackets are required)
• Because of the 0U PDU mounting, none of the 44U mounting space is lost.
• HCM-D42ES: optional cable management is available for each row of three PDUs and can
handle the 28 power cords to these PDUs
• A fourth cable management run can be installed on each side for any cable that needs to
be run from front to rear.
• A total of eight horizontal cable management runs can be installed front to rear.
• Each of these runs feed directly and uninterrupted into the rear vertical cable management
• The rear cable management runs are aligned with the pass through holes in the frame and
allow for easy cabinet-to-cabinet cable runs as well as from below or above.
• AT1:Retractable anti-tip legs mount to the outside
bottom of the frame and can be used when the
cabinet is on glides or casters.
• Retractability allows you to safely clear the aisle.
• If the cabinet is directly on the floor it should be
anchored. The anti-tip legs extend 10" out beyond the
front of the frame, this is the amount of extension
required due to the travel and weight of some servers.
• Mounting of the anti-tip legs is from the inside of the
cabinet through the bottom; a total of eight 1/4-20 bolts
are supplied.